+353 18 38 11 88 [email protected]

AFQm-3WF-300C-480

Category:
DESCRIPTION

Code: R7MF4F.

  •  System: 3 wires, 230…480 V
  •  Phase current: 300
  •  Peak current: 600
  •  Mounting: Floor-mounted

The wall-mounted AFQm multilevel active filters are the most complete solution for solving power quality problems in three-phase industrial, commercial or service installations caused by the presence of harmonics and the consumption of reactive power. These following characteristics and functions have been implemented:

  • Filtering capacity of 30 A, 60 A and 100 A
  • Small wall-mounted cabinet easy to install thanks to its small dimensions
  • Range for installations with 3 wires (3W model) or 4 wires (4W model)
  • Multi-range voltage and dual frequency (50/60 Hz)
  • Reduction of harmonic currents up to the fiftieth harmonic (2,500 Hz)
  • Selection of harmonic frequencies to be filtered for maximum filter effectiveness
  • Power factor correction both inductive and capacitive
  • Phase current balancing, improvement of consumption in neutral (4W model)
If higher filtering capabilities are required, up to 100 filters can be connected in parallel (the filters must all be of the same 3 or 4-wire model).

 

APPLICATIONS

They are an ideal solution for installations with a large amount of single-phase and three-phase loads generating harmonics, such as computers, UPS units, lights, lifting equipment, air-conditioning systems with variable speed drives, etc.
They can also be used in installations that require a good power quality for the purpose of increasing production efficiency and improve supply continuity in the system.

AC POWER SUPPLY
Installation category 4 kV, CAT III Class 1
Consumption 6210 W
Frequency 50 / 60 Hz (± 5 %)
Nominal voltage 208 … 480 V~ F-F (± 10 %)
 
MECHANICAL CHARACTERISTICS
Size (mm) width x height x depth 608 x 1890 x 812 (mm)
Envelope Free-standing sheet steel cabinet, for installation indoors, without removable parts.
Torque setting Grid and Neutral: 45 Nm / Earth: 10 Nm
Cable gauge at power supply terminals Neutral and Ground: Ø 12 mm,
Connection type Network: plate 40×10, Ground: Ring terminal 8 mm, Current: spring 2,5 mm2, Neutral: plate 100×10, Ethernet: RJ-45
Weight (kg) 300
 
ENVIRONMENTAL CHARACTERISTICS
Protection class IP 20 / IK10 (IP 54 on demand)
Relative humidity (without condensation) 0 … 95 %
Storage temperature -20 … +50 ºC
Operating temperature -10 … +45 ºC
 
ELECTRICAL CHARACTERISTICS
Conditional short-circuit current (Icc) 40 kA
Rated peak current Ipk 84 kA
Current crest factor 2:1
Maximum phase current 300 A (RMS)
Maximum neutral current 900 A (RMS)
Rated diversity factor (RDF), simultaneity 1
Earthing system TN, TT
 
CURRENT MEASUREMENT CIRCUIT
Transformation ratio 5 … 5000 / 5A
 
COMMUNICATIONS
Fieldbus (ModBus) RS-485
Stop bits (ModBus) 1
Parity non
Protocol Modbus RTU / Ethernet: TCP/IP, Modbus TCP
Speed 9600
 
STANDARDS
Electrical safety, Maximum height (m) 2000
Standards IEC 62477-1:2012, IEC 55011:2011, IEC 61000-6-2, IEC 61000-6-4:2007,IEC 61439-1:2011
 
USER INTERFACE
Display type TFT color, 3.5″ touchscreen
 
MEASUREMENT ACCURACY
Voltage harmonics (THD) 25 % (max)
 
FEATURES / PERFORMANCE
Phase compensation Selectable
Reactive power compensation (Kvar) Selectable
Filtering / Response time 2º … 50º harmonic (selectable) / < 100 µs
Parallel assembly/installation “Up to 100 units, with different gauges “Transformer connection only to the Master unit
Priority scheduling Selectable
 
POWER SUPPLY OUTPUT
Power 228900 VA