+353 18 38 11 88 [email protected]

computer SMART III Fast 6

DESCRIPTION

Code: R13951.

  •  Alarm relay: Yes
  •  Communications: RS-485
  •  Measurement Range (V): 100…520
  •  IΔn (A): yes
  •  Power supply (Vac): 100…520 Vac
  •  Nr steps: 6
  •  Input current: …/5A | …/1A
  •  Switching unit: EMF / EMB

Measurement with three current transformers guarantees an analogue reading of the company meter. The Computer SMART III Fast reactive energy regulator is the only regulator on the market that offers the possibility of using 3 measurement transformers in addition to the conventional method of measuring with a single current transformer, as well as providing the functions of an integral power analyzer and controlling residual leakage currents.
Computer SMART III Fast is a regulator that ensures excellent preventive maintenance by means of programming its alarms and the options for testing the capacitor status, offering maximum supervision and safety of your compensation unit.

APPLICATIONS

Computer Smart III fast it’s the ideal solution to compensate installations with a variation of quick load, between 40 ms and 4 seconds, and/or large unbalances between phases, such as welding units, cranes, lifts and lifting units, smelters, hospitals, automotive industry or any other sector or unit that requires an efficient compensation of the power factor.
The connection of 1 or 3 transformers makes computer SMART III Fast the perfect regulator in any installation, allowing the following:

  • Changing from 1 to 3 transformers in the following cases:
    • Single-phase fast changing equipment
    • Example: Single-phase welding
    • Replacing the regulator of any capacitor bank
  • Perfect for installations with up to 4 objective cos φ, since it can adapt to any compensation need (different time periods).
AC POWER SUPPLY
Installation category CAT III 300 V
Consumption 8 … 14 VA
Frequency 50 … 60 Hz
Nominal voltage 100 … 520 V ~
MECHANICAL CHARACTERISTICS
Size (mm) width x height x depth 144 x 144 x 71 (mm)
Envelope Plastic V0 self-extinguishing
Fastening Panel
Weight (kg) 0,44
ENVIRONMENTAL CHARACTERISTICS
Protection class IP 51 (Front), IP 31 (unmounted)
Relative humidity (without condensation) 5 … 95%
Storage temperature -20 … +70 ºC
Operating temperature -10 … +55 ºC
CURRENT MEASUREMENT CIRCUIT
Installation category CAT III 300 V
Nominal current (In) …/5A ó …/1A
Phase current measuring range 1 … 120 % In
Minimum current measurement 50 mA
VOLTAGE MEASUREMENT CIRCUIT
Installation category CAT III 300 V
Sampling frequency 45 … 65 Hz
Input impedance 660 kΩ
Voltage measuring range 20… 300V Ph-N, 35…520V Ph-Ph
Nominal voltage 230 V Ph-N, 400 V Ph-Ph
COMMUNICATIONS
Fieldbus (ModBus) RS-485
Parity non-pair-impar
Protocol Modbus RTU
Type CPC-NET / RS-485
Speed RS-485: 9600-19200 / CPC-NET: 9600-19200-38400
Stop bits 1-2
STANDARDS
Electrical safety, Maximum height (m) 2000
Standards IEC 61010, IEC 61000, IEC 61000-6-2, IEC 61000-6-4, Medidas conforme a : IEC 61557-12
USER INTERFACE
LED 4 LED
Keyboard Capacitive, 5 keys
Display type LCD Custom COG
DIGITAL INPUTS
Input/output insulation Optoisolated
Quantity 2
Type Potential-free contact
LEAKAGE CURRENT MEASUREMENT (ID)
Secondary nominal current 0,003 A
Minimum current measurement (Istart) 10 mA
Measurement range 0,01 … 1,5 A
OTHER DIGITAL TRANSISTOR OUTPUTS
Quantity 2
Type NPN
Maximum current 50 mA
Maximum voltage 24 Vcc
DIGITAL RELAY OUTPUTS
Quantity 2 (ventilador, alarma)
Maximum current 1A
Maximum open contact voltage 1 kV
Electrical life 30 x 103 ciclos
Mechanical life 5 x 106 Cycles
Maximum switching capacity 2500 VA
DIGITAL TRANSISTOR OUTPUTS
Quantity 6
Type Opto MOSFET
Maximum current 150 mA
Maximum voltage 24 Vcc
MEASUREMENT ACCURACY
Phase current measurement 0.5% ± 1 digit
Reactive energy measurement (kvarh) Class 2
Reactive power measurement (kvar) 1% ± 2 digit
Active energy measurement (kWh) Class 1
Phase voltage measurement 0.5% ± 1 digit