+353 18 38 11 88 [email protected]

CVM-E3-MINI-ITF-485-IC

DESCRIPTION

CVM-E3-MINI-ITF-485-IC, Power analyzer

Code: M56414.

  •  Protocol: Modbus/RTU | BACnet
  •  Communications: RS-485
  •  Transistor output: 1
  •  Digital inputs: 1
  •  Harmonics: 31
  •  Power supply (Vac): 207…253 Vac
  •  Input current: …/5 A | …/1 A
  •  Mounting: DIN rail

Three-phase power analyzer (balanced and unbalanced) for mounting on DIN rail, very compact, with measurements in 4 quadrants.

Other features:

  • Current measurement …/5 or …/1 A or …/250 mA or Rogowski type sensors
  • With ITF technology: ITF galvanic insulation protection
  • DIN rail with only 3 modules
  • High-contrast backlit display
  • 72 x 72 mm panel mounting with front adapter
  • RS-485 communication (Modbus/RTU up to 19.2 kbps) (Bacnet up to 19.2 kbps)
  • One transistor output (programmable)
  • One digital input for selecting tariff or logic states
  • Sealable terminal cover
  • Harmonic display (V, A) up to 31º
APPLICATIONS
  • Control application in low- and medium-voltage distribution panels and switchboards where it is necessary to place an analyzer on the DIN rail due to problems of space.
  • Alarm control. Maximum value, minimum value and programmable delay.
  • Control of active or reactive energy by impulse output.
  • Capture of maximum and minimum instantaneous data of electrical parameters measured.
AC POWER SUPPLY
Installation category CAT III 300 V
Consumption 4 VA
Frequency 50…60 Hz
Nominal voltage 207…253 Vc.a.
 
MECHANICAL CHARACTERISTICS
Size (mm) width x height x depth 52.5 x 118 x 74 (mm)
Envelope Self-extinguishing V0 plastic
Differential current measurement min. 2,5 mm2
Cable gauge at power supply terminals 1 mm2 (min.)
Cable gauge at voltage terminals mín. 1 mm2
Fastening DIN rail
Weight (kg) 0,38
 
ENVIRONMENTAL CHARACTERISTICS
Protection class IP 30 / Front: IP 40
Relative humidity (without condensation) 5…95%
Storage temperature -10 … +50 ºC
Operating temperature -5 … +45 ºC
 
CURRENT MEASUREMENT CIRCUIT
Installation category CAT III 300 V
Nominal current (In) …/5 A ó …/1 A
Phase current measuring range 2…120% de In
Maximum input current consumption 0,9 VA
Minimum current measurement 0,2 % In
 
VOLTAGE MEASUREMENT CIRCUIT
Installation category CAT III 300 V
Input impedance 400 kΩ
Frequency measuring range 45…65 Hz
Voltage measuring range 5 … 120 % Un
Nominal voltage 300V Ph-N, 520V Ph-Ph
Minimum measurement voltage (Vstart) 11 V Ph-N
 
COMMUNICATIONS
Fieldbus (BACnet) MS/TP
Fieldbus (ModBus) RS-485
Stop bits (BACnet) 1
Stop bits (ModBus) 1-2
Parity (BACnet) non
Parity non-pair-impar
Protocol ModBus/RTU, BACnet
Speed ModBus RTU: 9600-19200 bps / BACnet: 9600-19200 bps
 
STANDARDS
Electrical safety, Maximum height (m) 2000
Standards IEC 61010-1, IEC 61010-2-030, IEC 61326-1, IEC 61557-12 , UL94
 
USER INTERFACE
LED 2 LED
Keyboard 3 keys
Display type LCD Custom COG
 
DIGITAL INPUTS
Input/output insulation Optoisolated
Quantity 1
Type NPN Potential-free contact
 
DIGITAL TRANSISTOR OUTPUTS
Pulse width 30…500 ms (Programmable)
Type NPN
Maximum frequency 16 imp / s
Maximum current 50 mA
Maximum voltage 24 Vdc
 
MEASUREMENT ACCURACY
Frequency measurement 0,50%
Phase current measurement 0,5% ± 1 digit
Reactive energy measurement (kvarh) Class 2
Reactive power measurement (kvar) class 2
Apparent power measurement (kVA) 0.5 % ±2 digits
Active energy measurement (kWh) I < 0,1 In (Class 1) / I > 0,1 In (Class 0,5)
Active power measurement (kW) 0.5 % ±2 digits
Phase voltage measurement 0.5% ± 1 digit