Legrand Keor XPE

Category:

The Legrand Keor XPE is a modular scalable UPS system based on 250kVA or 300kVA power units that can be scaled up to 2.1MVA solution. Based on Online double conversion technolgy and using the finest component quality, the Legrand Keor XPE is an ideal UPS solution for data centres and large critical power applications where continuity of service and high quality power supply with low consuption is mission critical.

Download Brochure

  • Up to 7 power units of 250kVA or 300kVA
  • Flexible design and cabinet layouts
  • Intuitive 10″ touch screen
  • Top/bottom – cable/busbar connection
  • Lithium-ion battery compatible
  • Full communication interfaces
  • Redundancy and scalability
  • Hot serviceability
  • Up to 96.4% VFI efficiency
  • Compact footprint
  • Configuration up to 2N
WARRANTY 1 Year Parts (upgradable to 5 Years)
RATING KVA 600 – 2100
NOMINAL POWER 600Kw – 2100Kw
NO. OF POWER UNITS (+1 IF REQUIRED) 2+1(600kVA) 3+1 (750 -900 kVA) 4+1 (1000 – 1200kVA) 5+1 (1250 – 1500 kVA) 6+1 (1800 kVA)  7 (2100 kVA)
POWER UNIT POWER >300 Kw
DIMENSIONS (WxDxH) 2770 x 970 x 2100 (600kVA) 4090 x 970 x 2100 (750 -900 kVA) 4970 x 980 x 2100 (1000kVA) 5370 x 980 x 2100 (1200kVA) 6250 x 980 x 2100 (1250 – 1500 kVA) 7580 x 1200 x 2100 (1800 kVA)  8460 x 1200 x 2100 (2100 kVA)
TECHNOLOGY Online double conversion VFI-SS-111
ARCHITECTURE Decentralized Logic, Centralized Static Bypass, Scalable, Redundant, Hot Service (Hot Plug Optional)
WEIGHT 225KG (600kVA) 315KG (700kVA) 330KG (900kVA) 400KG (1000kVA) 425KG (1200kVA) 490KG (1250kVA) 520KG (1500kVA) 640KG (1800kVA) 730KG (2100kVA)
INPUT VOLTAGE TOLERANCE RANGE 380-400-415 V 3Ph+N 400 V -20% / + 15%
INPUT VOLTAGE 400 VAC 3-phase (rectifier), 380/400/415 Vac 3-phase (Bypass)
OUTPUT POWER FACTOR 1
INPUT FREQUENCY 50/60 Hz; range 45-65 Hz
THD OF INPUT CURRENT < 3%
COMPATIBILITY WITH DIESEL GENERATORS Yes
INPUT POWER FACTOR >0.99
OUTPUT VOLTAGE 380, 400, 415V (3Ph+N+PE)
OUTPUT FREQUENCY (nominal) 50 /60 Hz (Adjustable from front panel)
EFFICIENCY ONLINE Up to 96.4%
EFFICIENCY IN GREEN MODE >99%
OUTPUT FREQUENCY TOLERANCE  ±0,1%Synch with Mains; ±0,01% Free Run
CREST FACTOR up to 3:1
THD OF OUTPUT VOLTAGE < 1% at full linear load
OUTPUT POWER FACTOR 0.7 leading to 0.5 lagging without derating
OUTPUT VOLTAGE REGULATION VFI Static ± 1%; Dynamic Class1 IEC/EN62040-3
OVERLOAD CAPABILITY Inverter: 125% for 5 min, 150% for 30 sec;
BYPASS TYPE Static Automatic no break, Manual Bypass optional
BATTERY / STORAGE COMPATIBILITY VRLA, NiCd, Li-Ion
BATTERY CONNECTION Distribuited or Centralized
CONTROL PANEL DISPLAY Distribuited or Centralized
COMMUNICATION PORTS Serial RS232 and USB; ModBus-RTU (RS485). Net Card Slot (SNMP & ModBus-TCP/IP) (Optional)
INPUT SIGNAL PORTS AND AUX CONTACT Remote emergency power off (REPO), diesel mode, Temperature Probe, battery circuit breaker. Auxiliary contact of external circuit breakers: battery, external maintenance bypass, output remote transfer to bypass mode
OPERATING TEMPERATURE TOLERANCE 0 – 40 °C (Recommended temperature for longer Battery Life: 20-25°C
RELATIVE HUMIDITY 20-95% (Non-Condensing)