+353 18 38 11 88 [email protected]

Legrand trimod HE

Category:

With a unity power factor the Legrand Trimod HE UPS series guarantees a maximum real power. Each system provides three phase modularity consisting of individual, hot swappable, single phase modules allowing for optimised power availability and no need to power the UPS off.

Available from 10kVA to 80kVA the Legrand Trimod allows users to achieve an N+X redundancy. The batteries are sealed VRLA and can be arranged inside the UPS or within an external universal battery cabinet in dedicated draws to achieve longer runtimes.

Download Brochure

  • Hot swappable single phase 3,4,5 and 6.7kVA power modules
  • Small footprint with a high power density
  • Power factor 1 and high efficiency
  • Multi control board function
  • Dual input function
  • Plug & Play technology
  • Menu available in 7 languages
  • Frequency converter in 40-70Hz out 50/60Hz (can be selected by the user)
  • Operates with a power-supply unit
  • Three independent output phases
  • Eco Mode
  • EPS Mode
  • Adjustable output voltage with 1V intervals (190÷245V)
  • Bypass activation speed control
  • Events log with date and time
  • Overall historical data and for each individual power module
  • Automatic recognition of the power modules
WARRANTY 1 Year Parts (upgradable to 5 Years)
RATING KVA 10 – 60
DIMENSIONS (WxDxH) 414Wx628Dx1650-1370H (10-30kVA) 416Wx628Dx1370H(40-60kVA)
WEIGHT 155-120KG (10-20kVA) 181-146KG (30kVA) 146KG (40kVA) 165KG (60kVA)
INPUT PHASE Three Phase / Single Phase
INPUT VOLTAGE 380/400/415 3PH+N+PE (or 220,230,240 1PH)
INPUT VOLTAGE TOLERANCE RANGE 400V +15%/-20% – 230V +15%/-20% (10-20kVA) 400V +15%/-20% (30-60kVA)
INPUT FREQUENCY 45-65 Hz
OUTPUT OUTPUT PHASE Three Phase / Single Phase
OUTPUT POWER FACTOR 1
OUTPUT WAVEFORM Sinusoidal
OUTPUT VOLTAGE 380/400/415VAC
OUTPUT FREQUENCY 50/60 Hz selectable by the user ±2 % (standard), ±14 % (extended)
OUTPUT EFFICIENCY Up to 96%
BATTERY RUNTIME Dependent on battery capacity
BATTERY DC VOLTAGE VRLA – AGM / 240 Vdc
BATTERY CHARGE CAPACITY Smart charge technology. 3-stage advanced cycle
OPERATING TEMPERATURE TOLERANCE 0 – 40°C
RELATIVE HUMIDITY <95% (non-condensing)
COMMUNICATION 2 RS232 serial ports, 1 logical gate, 5 ports with dry contacts, 1 slot for interfaces
OPTIONAL COMMS extended VFC
PARALLEL N+X
FUNCTIONS multi control board, dual input, three independent output phases, ECO mode, EPS mode, Adjustable output voltage with 1V intervals, automatic recognition of power modules