+353 18 38 11 88 [email protected]

MYeBOX-1500- 4 FLEX-R45

DESCRIPTION

MYeBOX-1500- 4 FLEX-R45, Portable power analyzer with recording of quality events and transients

Code: M8405C0000A00

  •  Nr Sensors: 4 FLEX-R45
  •  Communications: Wi-Fi | 3G
  •  Transistor output: 2
  •  Digital inputs: 2
  •  No. of voltage measurement inputs: 5
  •  Measuring current Channels: 5
  •  Class: Class A

MYeBOX® is a range of portable analysers that can be configured from an app and/or a website to analyse and record electrical parameters, measure and record waveform transients and network quality parameters, as per the EN 50160 standard. The information is accessible remotely from the app and/or website. MYeBOX® measures and records electrical parameters in single-phase, two-phase or three-phase installations (with and without a neutral).
The app/website is connected to the device to display the measured data in real time, fully configure the device, start or stop the data recording, send the recorded data to the MYeBOX® Cloud platform, and even access the data from the memory to view it graphically or in table form. The remote connectivity lets you analyse the measured data from anywhere. The recorded data can also be sent to a data repository for further analysis in PowerVision Plus. The device can be configured locally using the capacitive keyboard and the on-screen menu options.

MYeBOX® 150 and MYeBOX® 1500 have the following features and functions:

  • 4 voltage measurement inputs (U1U2U3Un)
  • 4 current measurement inputs (I1I2I3In)
  • Measurement of the main electrical parameters
  • Measurement of network quality parameters
  • True RMS measurement (TRMS)
  • Measurement of consumption and generation (4Q)
  • Voltage quality event log, according to EN 61000-4-30
  • Transients log
  • Recording of the wave shape associated with the quality events and transients
  • Measurement according to EN 61000-4-30
  • Power supply is independent of the measurement
  • Recording of the wave shape for each recording period
  • LCD Screen
  • Capacitive keypad
  • Micro-USB port to download data
  • Automatic detection of clamps
  • Identification of phases with colours
  • Compatible with clamps with EEPROM
  • Recording of system events (EVA)
  • NTP synchronisation
  • Sending of alarms via e-mail
  • Wi-Fi communications (access point/terminal)

The MYeBOX® 1500 model also has:

  • 1 voltage measurement input Uref
  • 1 leakage current measurement input
  • 2 transistor inputs to centralise impulses / tariff / state
  • 2 transistor outputs for alarms
  • 3G communications
APPLICATIONS

MYeBOX can be used to:

  • Prepare complete studies of an electrical installation.
  • Analyse consumption, load curves, disturbances in the installation’s voltage, display wave shapes, harmonics study or flicker measurement, among other options.
  • Perform audits and analyses remotely.
AUXILIARY BATTERY POWER SUPPLY
Autonomy 2 h (without 3G), 50 min (with 3G)
Battery type Litio (3,7 Vc.c.)
Capacity 3700 mAh
Load temperature 0 … 40 °C
Load time 6 h
 
AC POWER SUPPLY
Installation category CAT II 300 V
Consumption 22…28 VA
Frequency 47…63 Hz
Nominal voltage 100…240 Vc.a.(Adaptador de alimentación de c.a.)
 
 POWERED BY CHARGER, ADAPTER
Output voltage 9 Vc.c.
Maximum power 20 W
 
SPECIFIC TECHNICAL CHARACTERISTICS OF CURRENT SENSORS
Linearity 2 % (10…200 % In)
Measurement range 100/1000/10000 A
 
STANDARDS
Certifications UL, CAN/CSA-C22.2 No. 61010-1, 3rd Edition, 2012-5, CE
Electrical safety, Maximum height (m) 2000
Standards Recycling European Directive 2002/96/EC, EN 61326-1, UL 61010-1, 3rd Edition, 2012-05-11, IEC 61010-1, 3rd Edition
 
CURRENT MEASUREMENT CIRCUIT
Installation category CAT III 600 V
Nominal current (In) Depending on the clamp
Phase current measurement Transformadores con salida 0,250 A ó 0,333 V
Phase current measuring range 1…200 % In
Maximum input current consumption 0,0004 VA
Maximum pulse current 3 x In A
Minimum current measurement Depending on the clamp
 
VOLTAGE MEASUREMENT CIRCUIT
Installation category CAT III 600 V
Consumption 0,15 VA
Sampling frequency 45…65 Hz
Input impedance 2,4 MΩ
Voltage measuring range 10…600 Vac
Minimum measurement voltage (Vstart) 10 V ac
 
COMMUNICATIONS
Band 2,4 GHz.
Networks UMTS/HSPA: 850/900/1900/2100 MHz. # GSM /GPRS /EDGE: 850/900/1800/1900 MHz.
Maximum output power UTMS/3G (Potencia Clase 3): 24dBM, GSM850/900 (Potencia Clase 4): 33dBM, GSM1800/1900 (Potencia Clase 1): 30 dBM.
Connection mechanism Wi-Fi
 
ELECTRICAL SAFETY
Insulation Double-insulated electric shock protection class II (IEC 61010-1)
 
DIGITAL INPUTS
Input/output insulation 2,7 kV
Quantity 2
Type Potential-free contact
Maximum short-circuit current 5 mA
Maximum open circuit voltage 4…9 Vdc
 
MEMORY
Format FAT 32
Write time 1s, 1m, 5m, 15m, 1h, 1d
 
DIGITAL TRANSISTOR OUTPUTS
Quantity 2
Type Opto MOSFET
Maximum current 90 mA
Maximum voltage 48 Vc.c.
 
MECHANICAL CHARACTERISTICS
Weight (kg) 4
 
INTERNAL BATTERY
Capacity 220 mAh
Type Litio
Useful life 10 años
Voltage 3 Vc.c.
 
MEASUREMENT ACCURACY
Current asymmetry (Ka) Class A (IEC 61000-4-30)
Voltage asymmetry (Ka) Class A (IEC 61000-4-30)
Current unbalance (Kd) Class A (IEC 61000-4-30)
Voltage unbalance (Kd) Class A (IEC 61000-4-30)
Frequency measurement Class 0,1 (45…65 Hz)
Phase current measurement class 0,2 (1…200 % In) (IEC 61557-12)
Reactive energy measurement (kvarh) Class 1 (IEC 62053-23)
Reactive power measurement (kvar) Class 1 ± 1 digit (IEC 61557-12) (Vn ac 230/110)
Apparent power measurement (kVA) class 0,5 ± 1 digit (IEC 61557-12) (Vn ac 230/110)
Active energy measurement (kWh) Class 0,5S (IEC 62053-22)
Phase voltage measurement Class 0.2 0,2 (10…1000 VF-N c.a.) (IEC 61557-12)
Pinst. Flicker 3 % (IEC 61000-4-15)
Pst Flicker 5 % (0,2 … 10Pst) (IEC 61000-4-15)
Current harmonics (THD) (up 50th) Class 1 (IEC 61000-4-7)